Daikin Air Conditioners Error Codes

Daikin air conditioner error codes

Malfunction Error CodeMalfunction ContentsPotential causesSystems
RASkyAirVRVPackageHRVChiller
Indoor UnitA0External protection device activatedExternal protection device connected to the terminal strip T1-T2 of indoor unit is activated   
A1Malfunction of indoor unit PCBMalfunction due to noise Defect of indoor unit PCB  
A3Malfunction of drain level control systemDrain piping clogging, improper drain piping work Defect of drain pump Defect of float switch   
A4Malfunction of freezing protectionShortage of water volume Low water temperature setting Defect of 26WL Defect of water temperature thermistor     
A5High pressure control in heating, freeze-up protection control in coolingClogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor     
A6Fan motor locked, overload, overcurrentDefect of connector contact Defect of indoor unit PCBDefect of fan motor  
A7Malfunction of swing flap motorFailure of swing flap motor Defect of indoor unit PCB Jammed swing mechanism/blade    
A8Malfunction of power supplyOvercurrent of AC input Defect of power supply voltage    
A9Malfunction of electronic expansion valve driveDefect of electronic expansion valve coil Defect of indoor unit PCB Defect of connector contact    
AAHeater overheat26WH is activated     
AFMalfunction of a humidifier systemWater leakage of humidifier (option) Failure of swing float switch Improper drain piping incline    
AHMalfunction of dust collector of air cleanerDefect of dust collecting element Defect of high voltage power supply unitStained insulator part Defect of indoor unit PCB   
AJMalfunction of capacity setting (Indoor unit PCB)Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB   
C1Failure of transmission (between indoor unit PCB and fan PCB)Defect of transmission of fan motor control driver    
C4Malfunction of liquid pipe thermistor for heat exchangerDefect of connector contact Defect of liquid pipe thermistor for heat exchanger  
C5Malfunction of gas pipe thermistor for heat exchangerDefect of connector contact Defect of gas pipe thermistor for heat exchanger   
C6Malfunction of fan motor control driverDefect of fan motor sensor system Defect of fan motor control driver    
C7Front panel driving motor faultDefect of front panel driving motor Defect of limit switch     
C9Malfunction of suction air thermistorDefect of connector contact Defect of thermistor for suction air  
CAMalfunction of discharge air thermistorDefect of connector contact Defect of thermistor for discharge air    
CCMalfunction of humidity sensor systemDefect of connector contact Defect of humidity sensor    
CJMalfunction of thermostat sensor in remote controllerDefect of remote controller thermistor Malfunction due to noise Defect of remote controller PCB   
Outdoor UnitE0Protection devices actuated (unified)Protection device connected to outdoor PCB actuated Defect of protection device connector contact   
E1Defect of outdoor unit PCBMalfunction due to noise Defect of outdoor unit PCB 
E3Actuation of high pressure switch (HPS)Dirty outdoor unit heat exchanger and suction filter Defect of HPS Clogged refrigerant piping Defect of connector contact  
E3System No.1 Actuation of high pressure switch (HPS)Dirty outdoor unit heat exchanger Clogged refrigerant piping Defect of HPSShortage of water volume Defect of connector contact     
Outdoor UnitE4Actuation of low pressure switch (LPS)Clogged refrigerant piping Shortage of gas Defect of connecting connector Defect of outdoor unit PCB  
E5Overheat of inverter compressor motorShortage of refrigerant amount Defect of connector contact Leakage of four way valve    
E5Inverter compressor motor lockInverter compressor lock Incorrect wiring   
E6STD compressor motor overcurrent/lockClosed stop valve STD compressor lock  
E6System No.1 Compressor overcurrentDefect of EXP. valve Defect of compressorShortage of refrigerant amount     
E7Malfunction of outdoor unit fan motorFaulty contact of fan motor connector Defect of fan motor Defect of fan motor driver 
E8Overcurrent of inverter compressorDefect of compressor Defect of outdoor unit PCB Defect of inverter main circuit capacitor Defect of power transistor     
E9Malfunction of electronic expansion valve coilDefect of electronic expansion valve Defect of connector contact Defect of outdoor unit PCB  
EAMalfunction of four way valveDefect of four way valve Defect of outdoor unit PCBShortage of gas Defect of thermistor     
ECMalfunction of entering water temperatureMalfunction of cooling water temperature Defect of thermistor Defect of outdoor unit PCB     
EFMalfunction of thermal storage unitDefect of electronic expansion valve of thermal storage unit Defect of thermal storage PCB     
F3Malfunction of discharge pipe temperatureShortage of gas Defect of connector contactClogged refrigerant piping Defect fo discharge pipe thermistor 
F6Abnormal high pressure in coolingDefect of outdoor unit fan motor Defect of electronic expansion valve Defect of heat exchanger thermistor Defect of outdoor unit PCB     
F6Refrigerant overchargedRefrigerant overcharged Disconnection of heat exchanger thermistorDisconnection of outdoor air thermistor Disconnection of liquid pipe thermistor    
H0Malfunction of sensor system of compressorHarness is disconnected, or defective connection Defect of PCB     
H1Malfunction of humidifier unit damperDefect of limit switch Defect of damper     
H3Malfunction of high pressure switch (HPS)Defect of high pressure switch Broken wire Defect of connector contact Defect of outdoor unit PCB  
H4Malfunction of low pressure switch (LPS)Defect of low pressure switch Broken wire Defect of connector contact Defect of outdoor unit PCB    
H5Malfunction of compressor motor overload thermistorDefect of connector contact Defect of compressor motor overload thermistor     
H6Malfunction of position detection sensorFaulty contact of compress or cable Defect of compressor Defect of outdoor unit PCB     
H7Malfunction of outdoor fan motor signalFaulty contact of fan wiring Defect of fan motor driverDefect of fan motor   
H8Malfunction of compressor input (CT) systemDefect of power transistor Defect of reactor Faulty wiring of inverter system Defect of outdoor unit PCB     
H9Malfunction of outdoor air thermistorDefect of connector contact Defect of thermistor for outdoor air 
HCMalfunction of (hot) water temperature thermistorDefect of connector contact Defect of outdoor unit PCB Defect of thermistor for water temperature    
HFAlarm in thermal storage unit with iceThermal storage group defective wiring Defect of setting Excess of thermal storage tank numbers    
HJMalfunction of thermal storage tank water levelLow water level Defect of switch setting Water level detecting sensor failure Defect of connector contact    
Outdoor UnitJ1Malfunction of pressure sensorDefect of pressure sensor connector contact Defect of pressure sensor Defect of outdoor unit PCB    
J2Malfunction of current sensor of compressorDefect of current sensor Defect of outdoor unit PCBDefect of compressor  
J3Malfunction of discharge pipe thermistorDefect of connector contact Defect of outdoor unit PCBDefect of discharge pipe thermistor 
J4Malfunction of low pressure equivalent saturated temperature sensor systemDefect of connector contact Defect of thermistor Defect of outdoor unit PCB (Multi-split, Super-multi )     
J5Malfunction of suction pipe thermistorDefect of connector contact Defect of outdoor unit PCBDefect of suction pipe thermistor 
J6Malfunction of heat exchanger thermistorDefect of connector contact Defect of outdoor unit PCBDefect of heat exchanger thermistor 
J7Malfunction of liquid pipe thermistor (Refrigerant circuit and others)Defect of connector contact Defect of outdoor unit PCBDefect of liquid pipe thermistor  
J8Malfunction of liquid pipe thermistor (Refrigerant circuit and others)Defect of connector contact Defect of outdoor unit PCBDefect of liquid pipe thermistor     
J9Malfunction of gas pipe thermistor (Refrigerant circuit and others)Defect of connector contact Defect of outdoor unit PCBDefect of gas pipe thermistor  
JAMalfunction of high pressure sensorDefect of connector contact Defect of outdoor unit PCBDefect of high pressure sensor  
JCMalfunction of low pressure sensorDefect of connector contact Defect of outdoor unit PCBDefect of low pressure sensor  
JEMalfunction of sub-tank thermistorDefect of connector contact Defect of outdoor unit PCBDefect of sub-tank thermistor     
JFMalfunction of heating thermistor for heat exchangerDefect of connector contact Defect of outdoor unit PCBDefect of heat exchanger thermistor     
JHMalfunction of oil temperature thermistorDefect of connector contact Defect of outdoor unit PCBDefect of oil temperature thermistor     
L0Malfunction of inverter systemShortage of power supply capacity Defect of inverter PCBDefect of power transistor     
L1Malfunction of inverter PCBDefect of compressor wiring Blown fuseDefect of outdoor unit fan motor Defect of inverter PCB    
L3Electrical box temperature riseFin temperature rise due to short-circuit Defect of power transistorDefect of outdoor unit fan Defect of outdoor unit PCB     
L4Malfunction of inverter radiating fin temperature riseFin temperature rise due to short-circuit Defect of fin thermistor  
L5Inverter instantaneous overcurrent (DC)Closed stop valve Defect of compressor  
L6Inverter instantaneous overcurrent (AC)Overcharge of refrigerant amount Defect of compressorShortage of power supply capacity Defect of inverter unit     
L8Overcurrent of inverter compressorAbnormal high pressure rise due to clogged refrigerant circuit and others Defect of compressor   
L9Malfunction of inverter compressor startupFaulty of pressure equalization Defect of compressor wiringDefect of compressor   
LAMalfunction of power transistorDefect of power transistor Defect of inverter PCBDefect of compressor     
LCMalfunction of transmission between outdoor unit PCB and micro-computerDefect of grounding connection Defect of outdoor unit PCBMalfunction due to noise     
LCMalfunction of transmission between control and inverter PCBDefect of connector contact Defect of inverter PCBMalfunction due to noise Defect of outdoor unit control PCB   
P0Shortage of refrigerant amount (thermal storage unit)Shortage of refrigerant Clogged refrigerant piping     
Outdoor UnitP1Power voltage imbalance, open phaseOpen phase Voltage imbalance between phases Faulty main circuit capacitor Defect of wiring contact  
P2Automatic refrigerant charge operation stopClosed stop valve Closed valve of refrigerant tank    
P3Malfunction of thermistor in electrical boxElectrical box temperature rise (ambient temperature rise) Defect of fin thermistor Defect of outdoor unit PCB    
P4Malfunction of radiating fin temperature sensorDefect of radiating fin thermistor Defect of wiring contact Defect of outdoor unit PCB  
P8Heat exchanger freezing protection during automatic refrigerant charging(Close the refrigerant cylinder. Start again from step 1.)    
P9Malfunction of fan motor (humidifier unit)Defect of fan motor Broken relay harnessDefect of outdoor unit PCB Defect of connector contact     
P9Automatic refrigerant charge operation completed    
PABroken wire of heater (humidifier unit)Defect of heater unit Defect of outdoor unit PCBDefect of thermistor     
PAEmpty refrigerant cylinder during automatic refrigerant chargingRefrigerant cylinder of master unit is empty    
PCEmpty refrigerant cylinder during automatic refrigerant chargingRefrigerant cylinder of slave unit 2 is empty    
PEAutomatic refrigerant charge operation nearly completed    
PHMalfunction of temperature (humidifier unit)Defect of heater unit Defect of thermistorDefect of connector contact Defect of outdoor unit PCB     
PHEmpty refrigerant cylinder during automatic refrigerant chargingRefrigerant cylinder of slave unit 1 is empty    
PJMalfunction of capacity setting (Outdoor unit PCB)Capacity setting adaptor is not installed Improper capacity setting adaptor Defect of outdoor unit PCB     
PJImproper combination between inverter and fan driverMistake of inverter PCB Mistake of control PCBMistake of inverter fan PCB    
SystemU0Shortage of refrigerantShortage of refrigerant Closed stop valveClogged refrigerant piping 
U1Reverse phase, open phaseReverse phase, open phase of power wiring Wrong wiring Defect of outdoor unit PCB 
U2Defect of power supply voltage or instantaneous power failureDefect of power supply voltage Instantaneous power failure Defect of wiring contact  
U3Check operation not executedCheck operation not executed    
U3Malfunction of transmissionMalfunction due to noise Defect of outdoor unit PCBWrong wiring     
U4Malfunction of transmission between indoor and outdoor unitDefect or indoor-outdoor transmission wiring Malfunction due to noise Defect of indoor unit PCB and outdoor unit PCB 
U5Malfunction of transmission between indoor unit and remote controllerDefect of remote controller wiring Defect of indoor unit PCB Malfunction due to noise Defect of remote controller main/sub setting
U6Malfunction of transmission between indoor unitsFaulty wiring Defect of indoor unit PCBMalfunction due to noise     
U7Malfunction of transmission between main body micro-computer – INV micro-computerHarness disconnection/broken wire between PCB Defect of outdoor unit PCB     
U7Malfunction of transmission between outdoor unitsDefect of wiring between outdoor units Defect of outdoor unit switch setting Defect of wiring between outdoor – thermal storage units   
U8Malfunction of transmission between remote controllersDefect of remote controller main/sub setting Defect of remote controller wiring Defect of remote controller PCB  
Others77System No. 1 Malfunction of fan inter lockDefect of relay contact Broken wire     
78System No. 2 Malfunction of fan inter lockDefect of relay contact Broken wire     
7ASystem No. 2 Malfunction of current sensor of compressorDefect of current sensor Defect of compressor Defect of outdoor unit PCB     
7CSystem No. 2 Malfunction of pump inter lockCooling water pump interlock actuated     
80Malfunction of entering water temperature thermistorDefect of connector contact Defect of entering water temperature thermistor     
81Malfunction of leaving water temperature thermistorDefect of connector contact Defect of leaving water temperature thermistor     
82System No. 1 Malfunction of refrigerant thermistorDefect of connector contact Defect of refrigerant thermistor     
83System No. 2 Malfunction of refrigerant thermistorDefect of connector contact Defect of refrigerant thermistor     
84System No. 1 Malfunction of heat exchanger thermistorDefect of connector contact Defect of heat exchanger thermistor     
85System No. 2 Malfunction of heat exchanger thermistorDefect of connector contact Defect of heat exchanger thermistor     
86System No. 2 Malfunction of discharge pipe thermistorDefect of connecting connector Defect of discharge pipe thermistor     
88System No. 2 Malfunction of discharge pipe temperatureShortage of gas Defect of discharge pipe thermistor Defect of connector contact Clogged refrigerant piping     
89Malfunction of brazed-plate heat exchanger freezingDirty heat exchanger Shortage of refrigerant amount Defect of thermistor     
8ASystem No. 2 Malfunction of leaving water temperature thermistorDefect of connector contact Defect of leaving water temperature thermistor     
8ESystem No. 1 Malfunction of suction pipe thermistor 1 for heatingDefect of connector contact Defect of suction pipe thermistor     
8FSystem No. 1 Malfunction of suction pipe thermistor 2 for heatingDefect of connector contact Defect of suction pipe thermistor     
8HAbnormal high hot water temperatureThree-way valve malfunction Defect of thermistor Defect of water temperature setting     
90Abnormal chilled water quantity, abnormal AXPShortage of water volume Disconnection of AXP     
91System No. 2 Malfunction of electronic expansion valveDefect of connector contact Defect of electronic expansion valve coil     
92System No. 2 Malfunction of suction pipe thermistorDefect of connector contact Defect of suction pipe thermistor     
94Malfunction of transmission (between heat reclaim ventilation unit and fan unit)Defect of fan unit PCB Defect of connecting wire between (1) and (2)     
95System No. 1 Malfunction of inverter systemDefect of fan inverter unit     
96System No. 2 Malfunction of inverter systemDefect of fan inverter unit     
97Malfunction of thermal storage unitDefect of thermal storage unit     
98Malfunction of thermal storage brine pumpActuation of thermal storage brine pump overcurrent (OC)     
99Malfunction of thermal storage brine tankLow water level of thermal storage brine tank     
SystemU9Malfunction of transmission (other system)Defect of communication between other indoor unit and outdoor unit Other indoor unit electronic expansion valve failure    
UADefect of indoor/outdoor power supplyWrong model connections Wrong PCB connectedImproper power supply Defect of PCB     
UAMalfunction of field settingMalfunction of field setting by remote controller Defect of remote controller wiring Defective connection of optional device Defect of indoor unit PCB     
UAImproper combination of indoor and outdoor unitsExcess of connected indoor units Malfunction of field setting Uncanceled service mode Defect of outdoor unit PCB   
UARemote temperature setting wire disconnectionRemote temperature setting wire disconnection Defect of connector contact     
UCMalfunction of setting of centralized controller addressAddress duplication of centralized controller   
UEMalfunction of transmission between indoor unit and centralized controllerMalfunction of wiring between indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB 
UFWiring and piping mismatchImproper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units   
UHMalfunction of systemImproper connection of transmission wiring between indoor- outdoor units and outdoor-outdoor units Defect of indoor and outdoor unit PCB (RA: Mismatching indoor and outdoor units, Defect of voltage, Freeze protection in other indoor unit(k)   
UJMalfunction of transmission (Accessory devices)Defect of accessory devices Faulty wiring    
M1Malfunction of centralized remote controller PCBDefect of centralized remote controller PCB
M8Malfunction of transmission between optional controllers for centralized controlOther centralized control power disconnection Centralized control reset switch ON Defect of transmission wiring Central remote controller address change
MAImproper combination of optional controllers for centralized controlImproper combination of optional controllers for centralized control More than one master controller is connected Faulty setting of centralized control Defect of centralized control
MCAddress duplication, improper settingAddress duplication of central remote controller
Others60External protection device actuatedActuation of external protection device Defect of output signal wiring Defect of control PCB     
64Malfunction of indoor air thermistorDefect of connecting connector Defect of thermistor for indoor air Defect of control PCB     
65Malfunction of outdoor air thermistorDefect of connector contact Defect of control PCBDefect of outdoor air thermistor     
6AMalfunction of damper systemDefect of connector contact Defect of damper motorDefect of limit switch Defect of control PCB     
70System No. 2 Compressor overloadShortage of refrigerant amount Defect of connector contact Leakage of four way valve     
71System No. 2 Compressor overcurrentShortage of refrigerant amount Short-circuit Defect of compressor     
72System No. 2 Fan motor overcurrentDefect of fan motor connector contact Defect of fan motor Defect of PCB     
73System No. 2 Malfunction of high pressure (HPS) actuatedDirty heat exchanger Clogged refrigerant piping Defect of HPSShortage of water volume Defect of connector contact     
74System No. 2 Malfunction of low pressure switch (LPS)Clogged refrigerant piping Shortage of gasDefect of connector contact Defect of LPS     
75System No. 2 Malfunction of low pressure sensorDefect of connector contact Defect of PCBDefect of low pressure sensor     
76System No. 2 Malfunction of high pressure sensorDefect of connector contact Defect of PCBDefect of high pressure sensor     

Daikin Air Conditioner Error Codes Troubleshooting

  • No Power/Light Off:

    • Check if the fuse has blown.
    • Ensure power is connected and no power failure occurred.
    • Replace remote controller batteries.
    • Check if the timer is set correctly.
  • Not Heating or Cooling Properly:

    • Set temperature and mode correctly.
    • Clean air filters.
    • Ensure nothing is blocking airflow.
    • Close windows and doors.
    • Check if ventilation fan is working.
  • Unit Stopped, Light Flashing:

    • Clean air filters and restart.
    • Remove any obstructions around indoor and outdoor units.
  • Odour from Unit:

    • Minor ozone smell during purification—harmless.
    • Mould-proof function can cause odour in humid conditions.
  • Remote Display Fading:

    • Replace batteries (use alkaline; lasts about a year).
  • Operate Without Remote:

    • Press ON/OFF button on the main unit for auto mode.
  • Water Leaking Indoors:

    • Turn off and unplug unit.
    • Contact a technician.